877-349-4184

KN-L Series

CHP Model #

Electrical Power 58
System Efficiency 86.4%
Thermal Power 303,000
NOX (G/BHP-H) < 0.1
Heat Rate BTU/kWe 10,017
CO (G/BHP-H) < 0.6
Electrical Power 80
System Efficiency 86.7%
Thermal Power 418,000
NOX (G/BHP-H) < 0.1
Heat Rate BTU/kWe 9,987
CO (G/BHP-H) < 0.6
Electrical Power 150
System Efficiency 87.5%
Thermal Power 711,000
NOX (G/BHP-H) < 0.1
Heat Rate BTU/kWe 9,326
CO (G/BHP-H) < 0.6
Electrical Power 285
System Efficiency 89.3%
Thermal Power 1,389,000
NOX (G/BHP-H) < 0.1
Heat Rate BTU/kWe 9,442
CO (G/BHP-H) < 0.6
Electrical Power 239
System Efficiency 87.3%
Thermal Power 1,073,000
NOX (G/BHP-H) < 1.0
Heat Rate BTU/kWe 9,037
CO (G/BHP-H) < 0.7
Electrical Power 373
System Efficiency 85.3%
Thermal Power 1,565,000
NOX (G/BHP-H) < 1.0
Heat Rate BTU/kWe 8,922
CO (G/BHP-H) < 1.0
Electrical Power 430
System Efficiency 85.9%
Thermal Power 1,880,000
NOX (G/BHP-H) < 1.0
Heat Rate BTU/kWe 9,060
CO (G/BHP-H) < 1.0
Electrical Power 550
System Efficiency 86.6%
Thermal Power 2,408,000
NOX (G/BHP-H) < 1.0
Heat Rate BTU/kWe 9,014
CO (G/BHP-H) < 1.0

NATURAL GAS LEAN-BURN CHP MODULES

Lean and clean, the KN-L Series delivers the benefits of higher efficiency lean-burn engine technology and still produces low exhaust emissions without after-treatment. Our broadest range of Natural Gas CHP Modules, the KN-L Series includes 7 models, each configurable for indoor or outdoor installation. Compact and pre-engineered to reduce installation time and costs.

Specification SHeet

MORE DETAILS BELOW

Even lower NOx emissions tuning is available for specific applications in addition to simple CO mitigation to avoid the expense of SCR after-treatment

The Kraft Energy Systems Advantage

  • Over 50 Years of Power Generation Experience
  • Pre & Post Sale – Engineering Support
  • Long Term Service Agreements
  • 24 x 7 Parts & Service Lower Energy Cost
  • Environmentally Responsible
  • Reliable, Fuel Efficient Industrial Engine
  • Fully Automated & User Friendly Control System with Remote Access & Monitoring
  • Compact Standardized Designs
  • Quiet Indoor and Outdoor Enclosure Design
  • Hot Water or Recovery
  • Pre-manufactured Modules Reduce Installation Cost
  • Standardized Utility Inter-tie Controls, Relay Options Available
  • Low Exhaust Emissions Without Aftertreatment*
  • Lean Burn Models from 64 kWe – 550 kWe
CHP Unit Model KN-60L KN-100L KN-180L KN-240L KN 375L KN 430L KN 550L
Man Engine Model
E 0834 LE302
E 0836 LE302
E 2676 LE202
E 2676 LE202
E 3268 LE212
E 3262 LE232
E 3262 LE202
Generator Model
LSA 44.3 S3
LSA 44.3 M6
CLSA 46.3 S4
LSA 46.3 M7
LSA 47.2 S5
LSA 47.2 M7
LSA 49.3 S4
Electric Output
kWe
64
104
180
239
373
430
550
Amps @ 600V @ 0.8 PF
Amps
77
125
217
287
449
517
662
Amps @ 480V @ 0.8 PF
Amps
96
156
271
359
561
647
827
Fuel Consumption (LHV)
BTU/hr
613,000
988,000
1,690,000
2,160,000
3,328,000
3,896,000
4,958,000
Engine Horsepower
BHP
91
148
254
335
523
603
778
No. of Cylinders/Arrangement
4/IL
6/IL
6/IL
6/IL
8/V
12/V
12/V
Bore & Stoke
in
4.25 x 4.92
4.25 x 4.92
4.96 x 6.54
4.96 x 6.54
5.20 x 6.18
5.20 x 6.18
5.20 x 6.18
Displacement
cu in
279
319
757
757
1,049
1,573
1,573
BMEP
psi
172.6
155.2
149.9
197.3
219.4
168.2
217.5
Compression Ratio
11:1
11:1
12.6:1
12.6:1
12:1
12:1
12:1
Electric Efficiency
%
35.2
36.0
36.4
37.7
38.3
37.7
37.9
Thermal Efficiency
%
51.0
49.9
48.1
49.7
47.0
48.2
48.7
Combined Efficiency
%
86.3
85.9
84.5
87.3
85.3
85.9
86.6
Thermal Output
BTU/hr
315,000
493,000
813,000
1,073,000
1,565,000
1,880,000
2,408,000
Process Water Flow @ 32ºF rise
GPM
20
31
51
68
99
119
152
Process Water Flow @ 20°F rise
GPM
32
51
83
110
160
192
246
Process Water Temperature
ºF
190 or 180
190 or 180
190 or 180
190 or 180
190 or 180
190 or 180
190 or 180
Sound Level @ 1m
dB(A)
75 +/- 3
75 +/- 3
75 +/- 3
75 +/- 3
75 +/- 3
75 +/- 3
75 +/- 3
Exhaust Flow
lbs/hr
809
1,329
2,384
3,122
4,630
5,338
6,919
Exhaust Temperature
ºF
248
248
248
248
248
248
248
NOx emission*
g/BHP-hr
< 1.0
< 1.0
< 1.0
< 1.0
< 1.0
< 1.0
< 1.0
CO emission*
g/BHP-hr
< 0.7
< 0.7
< 0.7
< 0.7
< 1.0
< 1.0
< 1.0
NMHC emission*
g/BHP-hr
< 0.1
< 0.1
< 0.1
< 0.1
< 0.1
< 0.1
< 0.1
Gas Pressure (Min)
in WC
10
10
10
10
10
10
10

* Correlation 15% O2. Lower NOx levels possible on request
Tech Data is based on Natural Gas with a calorific value of 970 Btu/ft3 and a methane No. >80.

The Tech Data is based on standard conditions in accordance with DIN ISO 3046-1. Atmospheric pressure: 14.5 psi or 328 ft above sea level, Air Temperature: 77 deg F, Relative Humidity: 30%
Tolerances: Fuel Consumption + 5%, Thermal Output +/- 8%

Sound Level Rating applies to Indoor Enclosed Module. Sound Level Rating applicable to Outdoor Enclosed Module is 65 dB(A) +/- 3 @ 10 m Heat transfer data is based on 40% antifreeze.